공동주택 저부하 조건에서 콘덴싱 보일러의 숏사이클링 운전 특성 분석

공동주택 저부하 조건에서 콘덴싱 보일러의 숏사이클링 운전 특성 분석

저자

방민규, 김찬규, 송용민, 백승효, 여명석

저널 정보

대한설비공학회 2026 하계학술발표대회논문집

출간연도

2026

링크

Abstract

Condensing boilers achieve high efficiency through latent heat recovery; however, oversizing can lead to efficiency loss due to short cycling. This study investigates short cycling in a residential apartment. Under low-load conditions, the flow rate decreases to approximately 1.2 L/min, causing the supply water temperature to rise to about 90°C and triggering boiler shutdown due to overheating. As the indoor temperature has not reached the setpoint, repeated restart and shutdown cycles occur, resulting in short cycling. Consequently, the average supply temperature (~67.5°C) fails to meet the target. Maintaining a minimum flow rate and considering flow conditions in boiler sizing are essential to prevent short cycling.

Key Words

Condensing Boiler(콘덴싱 보일러); Short Cycling(숏사이클링); Low Load(저부하)